Votre leader canadien en instrumentation depuis 1946.

Contrôleur de température à point de consigne unique

Controller 48x48mm (1/16 Din), single control loop. Basic temperature controller available in one single ordering code. Input selectable for different temperature sensors; one relay or SSR output, programmable as command/alarm/event output.  Extended supply range  24….230 Volt ac/dc galvanically isolated. User-friendly operation, programming tools for quick set-up (MEMORY-CARD, programming and monitoring software […]

  • SKU : I-975-ATR236
Posez une question sur ce produit

Controller 48x48mm (1/16 Din), single control loop. Basic temperature controller available in one single ordering code.


Input selectable for different temperature sensors; one relay or SSR output, programmable as command/alarm/event output.  Extended supply range  24….230 Volt ac/dc galvanically isolated.


User-friendly operation, programming tools for quick set-up (MEMORY-CARD, programming and monitoring software LABSOFTVIEW).


Main features


Box: 48×48 (front panel) x 107 mm


Power supply: 24…230Vac/dc ±15% 50/60 Hz (galvanic insulation)


Consumption: 5,0 VA, 4W


Display: 4 digits 0,4" green + 4 digits 0,3" red


Operating conditions: Temperature 0-45 °C, humidity 35..95 uR%



Material


Box: Noryl UL94V1 self-extinguishing, front panel: PC ABS UL94V0 self-extinguishing


Weight: Approx. 165 g


Sealing: IP65 (Front panel) , IP20 (Box and terminal bloks)


Quick set-up options: Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes


Inputs


1 Configurable: Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K)


Sampling time: 4,1 ms (frequency 242 Hz)


Outputs


1 Relay: Relay 5 A – 250 Vac resistive charge


1 SSR: 12 Vdc – 30 mA max


Software features


Control algorithms: ON – OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned


Tuning: Manual or automatic


Data protection: Lock of control / alarm setpoint, Access to parameters by password


Alarm modes: Absolute / Threshold, band, high / low deviation. Alarm with optional manual reset


Auto / Man function: Command output percentage


Soft-Start: Rising gradient expressed as Degrees / Hour