Votre leader canadien en instrumentation depuis 1946.

Contrôleur PID multipoints / convertisseur de signal

DIN rail-mounted Controller, single control loop. Distinctive feature is the high configurability available in a single ordering code. Beside operation as multi-setpoint PID controller, the unit can be ideally used as signal converter thanks to universal analogue input (selectable by parameter for up to 18 different signals) and the analogue output which is […]

  • SKU : I-975-DRR245
Posez une question sur ce produit

DIN rail-mounted Controller, single control loop. Distinctive feature is the high configurability available in a single ordering code.


Beside operation as multi-setpoint PID controller, the unit can be ideally used as signal converter thanks to universal analogue input (selectable by parameter for up to 18 different signals) and the analogue output which is galvanically isolated and programmable for rescalable retransmission of process/setpoint value.


RS485-ModbusRTU, Loop Break Alarm by current transformer.


User-friendly interface for the operator, programming tools available for quick set-up (MEMORY-CARD, programming and monitoring software LABSOFTVIEW).


Main features


Box: DIN43880, DIN EN50022 rail mounted


Power supply: 24…230Vac/dc ±15% 50/60 Hz (galvanic insulation)


Consumption: 3 W


Display: 4 digits 0,4" green + 4 digits 0,3" red


Operating conditions: Temperature 0-45 °C, humidity 35..95 RU%



Material


Box: Polycarbonate V0; Front panel: Silicon V0


Weight: Approx. 195 g


Sealing: IP65 (Front panel) , IP20 (Box and Terminal blocks)


Quick set-up options: Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes


Wiring: With terminal extension


Inputs


1 configurable: Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,0…40mV, Potentiometer 1…6/160 Kohm, T.A (1024 points)


Sampling time: Programmable up to 4,1 ms (Frequency up to 242 Hz)


1 T.A. input: Selection T.A. 50 mA – 100 msec – 1024 points


1 Digital input: 1/2…4 setpoints selection , Hold, Run, Tuning launch, Start/stop cycle


Outputs


2 Relays: Relays 5 A – 250 Vac resistive charge


1 SSR: 12 Vdc – 30 mA max


1 Analogue: Selection 4 – 20 mA or 0 – 10 Vdc for command or retransmission PV/SPV


Serial communication: RS485 Modbus RTU – Slave


Software features


Control algorithms: ON – OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned


Tuning: Manual or automatic


Data protection: Lock Command / alarm setpoint


Alarm mode: Absolute / Threshold, band, High / Low deviation. Loop Break Alarm function


Auto/Man function: Output percentage command also with automatic change in case of sensor failure


Double P.I.D.: Heating / Cooling P.I.D.


Programmer function: Start/Stop pre-programmed cycle with 2/3 steps


Soft-Start: Rising gradient expressed as Degrees / Hour