Onset
SKU: T-DCI-F900-S-P
Air Velocity Sensor (0.15 to 10 m/s) (30 to 1969 fpm) Sensor
$513.00
Important Info
+Overview
The F900 S-P Airflow Sensor is designed to measure the velocity of airflows in applications such as HVAC, industrial processes, automotive, air filtration systems, electronics enclosures and critical containment areas.
Requires analog port selection during U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1).
Highlighted Features
- This adds the ability for users to be able to measure air velocity (in ducts, e.g.) from which CFM can be computed.
In what environment does this sensor operate?
This sensor operates in an indoor environment.
What measurements does this sensor support?
The T-DCI-F900-S-P sensor supports the following measurement: Air Velocity
Specifications
+| Measurement range "O" model: | 0.15 - 5 m/s (30 - 985 fpm) |
| Measurement range "P" model: | 0.15 - 10 m/s (30 - 1969 fpm) |
| Accuracy: | Greater of 10% of reading or +/-0.05 m/s or 1% full-scale |
| Standard medium: | Air at standard pressure (101.3 kPa, 29.95" Hg) |
| Operating temperature range: | 15 "‚¬œ 35 C (59 "‚¬œ 95 F) |
| Storage temperature: | -10 to 100C |
| Supply voltage: | 7-13 VDC |
| Supply current: | 40 - 75 mA (10K ohm nominal) |
| Warm-up time: | < 5 sec |
| Response time: | 1.5 sec |
| Output: | Linear 0 - 4 VDC full scale for calibrated range, up to 4.9 VDC beyond calibrated range |
| Sensor head material: | Plastic |
| Dimensions: | 100 mm x 12 mm diameter for "S" model, 91 mm x 12 mm for "L" model |
| Weight: | "S" model 1 oz., "L" model 1.8 oz. |
| Vibration: | Up to 25 G |
| Acceptable angle: | +/- 300 from perpendicular |
| Repeatability: | +/- 1% under same conditions |
Attributes
+| Environment | Indoor |
|---|