Configurable Ultrasonic Level Sensors for Water & Benign Liquids Liquid Tight, Multiple Output, PVC Threaded Housing These small sensors are designed for level control of water and other benign liquids. They measure liquids at distances from 12-inches to 50 ft. (15.2 m). Adjustment is made using SenixVIEW software to set powerful extended features, then view, […]
Configurable Ultrasonic Level Sensors for Water & Benign Liquids
Liquid Tight, Multiple Output, PVC Threaded Housing
These small sensors are designed for level control of water and other benign liquids. They measure liquids at distances from 12-inches to 50 ft. (15.2 m). Adjustment is made using SenixVIEW software to set powerful extended features, then view, analyze and maintain setups. Tested setups can be stored and recalled to quickly duplicate applications without calibration − ideal for OEM or maintenance operations where time saving is important. Multiple standard interfaces and functions means a single TSPC-25P sensor is adaptable to many tank sizes, reducing part numbers and inventory.
Key Benefits and Features:
Survives in Tough Environments
Easy to Install and Use
Enhanced Sensor Capabilities with SenixVIEW
By model ► |
TSPC-25P-232 | TSPC-25P-485 |
Tank Networks | No | Yes |
Serial Data Interface | RS-232 | Addressable RS-485, multi-drop |
Modbus and ASCII streaming protocols | ||
Range, Optimum Range, Maximum |
9.1 m (30 feet) 15.2 m (50 feet) |
|
Deadband | 30.5 cm (12 inches) | |
Repeatability | Nominal 0.2% of range at constant temperature | |
SenixVIEW enhanced capabilities |
Adjustment: Over 60 functionally organized sensor parameters Viewing: Large and small displays, chart, filtered & unfiltered Analysis: Measure statistics; log and replay data, view in Excel Maintenance: Store, retrieve and document setups |
|
Adjustable features | Output calibration & polarities, rate, filter, temp comp, no target, more. | |
Outputs (Simultaneous) | Analogs (3): Voltage (0-10 VDC). 4-20 mA sourcing, 4-20 mA sinking Switches (2): Each software selected as PNP or NPN All outputs proportional to or affected by measured distance Reversible analog slope and switch polarities |
|
Measure Rate (nom) | 5 Hz (200 ms interval), SenixVIEW adjustable | |
Input Power | 10-30 VDC, typical 24 VDC | |
Environmental | Temperature -40 to 70C, humidity 0-100% operating | |
Protection | IP68, NEMA-4x, NEMA-6P | |
Compliance |
||
Housing | PVC, potted and sealed, liquid tight | |
Size (diameter x length) | 2.5 x 5 inches (64 x 127 mm) | |
Mounting | 2-1/2-inch NPT threaded top and bottom | |
Cable | 9-wire, UV resistant, 6-ft (2m) length, permanently attached | |
These products are not recommended for applications with hazardous or explosive materials, or as a primary device for personal safety! |