Canada’s Instrumentation Leader Since 1946.

10-100 Amp split-core AC current Sensor

$222.00

A split-core AC current sensor responsive over the range of 10 to 100 amps AC for use with U12, UX120, and ZW data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Ask us about this item

This split-core sensor records AC amperage; for use with HOBO U12, UX120-006M, MX1100, and ZW series external-channel data loggers. With an input of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Highlighted Features

  • UL listed
  • Sensor power induced from line voltage
  • Self-gripping split-core design for fast installation

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The CTV-C sensor supports the following measurement: AC Current

Specifications

Range: 10-100 Amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)