Canada’s Instrumentation Leader Since 1946.

Analog Node 4 Channels

MAIN SPECIFICATIONS Each channel is individually congured by the user. Power supply: 5 V DC / 12 V DC / 24 V DC up to 60 mA selectable for each channel. VOLTAGE Measuring ranges [V DC]: +/-10 ; +/-1.25 (8x). Accuracy (-40 to +85ºC): +/- 0.05 % FS. CURRENT LOOP (2-3 WIRES) Measuring range: 4-20 […]

  • SKU : GK96-LS-G6-ANALOG-4
Ask us about this item

MAIN SPECIFICATIONS

Each channel is individually congured by the user.

Power supply: 5 V DC / 12 V DC / 24 V DC up to 60 mA selectable for each channel.

VOLTAGE

  • Measuring ranges [V DC]: +/-10 ; +/-1.25 (8x).
  • Accuracy (-40 to +85ºC): +/- 0.05 % FS.

CURRENT LOOP (2-3 WIRES)

  • Measuring range: 4-20 mA.
  • Accuracy (-40 to +50ºC): +/- 0.05 % FS.

POTENTIOMETER (POT)

  • Accuracy (0 to +50ºC): +/- 0.02 % FS.

FULL WHEATSTONE BRIDGE (FWB)

  • Accuracy (0 to +50ºC): +/- 0.1 % FS.

THERMISTOR

  • Accuracy (0 to +50ºC): +/- 0.2ºC.

PT 100

  • Accuracy (20ºC): +/- 0.8ºC.

MECHANICAL

  • SIZE 145 x 220 x 61 mm
  • WEIGHT 1.100 g without batteries.
  • HOUSING MATERIAL Aluminium alloy
  • WEATHER PROTECTION IP67

BATTERY LIFE ESTIMATION*

Channels & Sampling Current @12V@24mA Current @24V@24mA Voltage @12V@24mA FWB@[email protected]Ω FWB@[email protected]Ω
Warm uptime 1 second 1 second 1 second    
1 CH 5 min. 6 months 4 months 5 months 1.5 years 1.5 years
1 CH 6 hours >10 years >10 years >10 years 8.5 years >10 years
4 CH 5 min. 1.5 months 39 days 2 months 1.5 months 7 months
4 CH 6 hours 8 years 6.5 years >10 years 8.5 years >10 years
*Estimations for 4 x saft LSH 14 batteries. Considering laboratory.

ACCESSORIES

  • Saft LSH 14 C-size spiral cell (code: LS-ACC-CELL-1C)
  • Datalogger-mobile cable (code: LS-ACC-MUSB-OTG)
  • External mounting brackets (set of 2) for wall mounting (code: LS-MEC-MP-001)
  • Plate for pole mounting. Includes: U-bolts and nuts for a pole diameter of less than 50 mm (code: LS-ACC-POLE50) or of less than 35 mm (code: LS-ACC-POLE35)