$222.00
Records state changes, electronic pulses, and mechanical or electrical contact closures from external sensing devices.
Records state changes, electronic pulses, and mechanical or electrical contact closures from external sensing devices. Ideal for monitoring energy consumption, mechanical equipment operation, and water and gas flow.
Highlighted Features
In what environment does this data logger operate?
This data logger operates in an indoor environment.
What measurements does this data logger support?
The UX90-001 data logger supports the following measurements: Event, Kilowatt Hours (kWh), Motor On/Off, Pulse Input, Runtime, State Open/Closed and Water Flow
Internal Sensor | |
---|---|
Maximum state, event, runtime frequency: | 1 Hz |
Preferred switch state: | No magnet present (normally open) |
External Input | |
External contact input: | Electronic solid state switch closure or logic driven voltage output |
Range: | 0 to 3 V DC (USB powered), 0 to 2.5 V DC (battery powered) |
Maximum pulse frequency: | 50 Hz |
Maximum state, event, runtime frequency: | 1 Hz |
Pulse, event lockout time: | 0 to 1 second in 100 ms steps |
Solid state switch closure: | Input Low: < 10 KΩ; Input High: > 500 KΩ |
Internal weak pull-up: | 100 KΩ |
Input impedance: | Solid state switch closure: 100 KΩ pull up |
Logger | |
Resolution: | Pulse: 1 pulse, Runtime: 1 second, State and Event: 1 State or Event |
Logging rate: | 1 second to 18 hours, 12 minutes, 15 seconds |
Time accuracy: | ±1 minute per month at 25°C (77°F) (see Plot A) |
Battery life: | 1 year, typical with logging intervals greater than 1 minute and normally open contacts |
Memory | |
UX90-001: | 128 KB (84,650 measurements, maximum) |
UX90-001M: | 512 KB (346,795 measurements, maximum) |
Download type: | USB 2.0 interface |
Download time: | 10 seconds for 128 KB; 30 seconds for 512 KB |
Logger Operating Range | |
Logging: | -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing) |
Launch/readout: | 0° to 50°C (32° to 122°F) per USB specification |
LCD: | ± 1 minute per month at 25°C (77°F) |
LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range: | Approximately 45 seconds; may take longer the farther the device is from the logger |
Weight: | 23 g (0.81 oz) |
Environmental rating: | IP50 |
The CE Marking identifies this product as complying with all relevant directives in the European Union (EU). |